묘사:
Diesel Engine Generator Set
MRC:
The cooling medium used to maintain the required operating temperature of the prime mover.AAXS
Prime Mover Cooling Medium:
Liquid
MRC:
Indicates the type of mount utilized to support the item.AAXX
Mounting Type:
Base
MRC:
The dimension measured along the longitudinal axis with terminated points at the extreme ends of the item.ABHP
Overall Length:
137.594 inches
MRC:
The distance measured in a straight line from the bottom to the top of an item.ABKW
Overall Height:
70.500 inches
MRC:
An overall measurement taken at right angles to the length of an item,in distinction from thickness.ABMK
Overall Width:
51.938 inches
MRC:
Indicates the type of current whether alternating,direct,or both.ACDC
Current Type:
Ac
MRC:
The number of complete cyclic changes,per unit of time,for which an item is rated.ACZB
Frequency Rating:
60.000 hertz
MRC:
The means of cooling used to maintain the required operating temperature of the item.AENK
Cooling Method:
Heat exchange
MRC:
The maximum weight that the item is designed to support.AERL
Maximum Weight Capacity:
10000.000 pounds
MRC:
The number of parts supplied with the item which may be required for application.AFHS
Accessory Component Quantity:
1 and 1 and 1 and 1 and 1 and 1 and 1 and 1 and 1 and 1
MRC:
The name of the government agency or commercial organization that controls the manufacture of the accessory item.AKVY
Accessory Controlling Agency:
Rwestinghouse electric corp; leece neville co; ross heater and mfg co; westinghouse electric corp; westinghouse electric corp; westinghouse electric corp; maxim silencer co; westinghouse electric corp; navship; navship
MRC:
The specific number used to identify the accessory.AKVZ
Accessory Identifying Number:
1-jh-688 drawing no. And s-22985 drawing no. And 8258cp drawing no. And 1-jh-1081pc1 drawing no. And 1-jh-1081pc3 drawing no. And 1-jh-1081pc4 drawing no. And 12-6-11515d drawing no. And 1-jh-1080 drawing no. And s17-g-22160-525-007 part no. And s17-g-22160-525-008 part no.
MRC:
An identifying number assigned by the government agency or commercial organization controlling the item.AMSB
Identifying Number:
Dwg no. 1-jh-1836
MRC:
An indication of whether or not winterization is included.AMWJ
Winterization Feature:
Not included
MRC:
The name of the manufacturer.AQGA
Manufacturer Name:
Westinghouse electric corp
MRC:
The alternating current for which the item is rated,expressed in watts.AYGY
Ac Wattage Rating:
185.000 kilowatts
MRC:
The total electrical line to line voltage for which the item is rated,expressed in volts.AYHB
Line To Line Voltage In Volts:
450.000
MRC:
The ratio between actual rated power,and power required by a specified load applied to the item,expressed in percent.AYHD
Power Factor In Percent:
0.8
MRC:
Indicates the type of excitor provided.AYHE
Excitor Type:
Separately excited
MRC:
An indication of whether or not an excitor is included.AYHF
Excitor:
Included
MRC:
The means used to start the prime mover.AYQZ
Prime Mover Starting Method:
Compressed air
MRC:
An indication of whether or not an automatic starting feature is provided.AZBM
Automatic Starting Feature:
Not provided
MRC:
The name of the manufacturer of the prime mover.AZBN
Prime Mover Manufacturer Name:
Packard motor car co
MRC:
The number used by the manufacturer for identifying the prime mover.AZBP
Prime Mover Identifying Number:
Model no. 2d-850-r3
MRC:
Indicates the type of housing provided.AZCB
Housing Type:
Open
MRC:
The name of the accessory component assigned by the controlling agency.AZCG
Accessory Component Name:
Generator, dc; starting motor, a1r; heat exchanger; static exciter; control panel; transformer; muffler, engine; regulator, voltage; mechanical repair parts and tools; electrical repair parts
MRC:
The ambient temperature of the medium surrounding an item at which it can be operated,expressed in degrees celsius.AZCL
Ambient Tempurature In Deg Celsius:
50.000
MRC:
The permissible temperature increase for continuous operation,at which the item is rated,expressed in degrees celsius.AZCM
Tempurature Rise Rating In Deg Celsius For Continuous Operation:
40.000
MRC:
An indication of whether or not radio interference suppression is included.AZKT
Radio Interference Suppression:
Not included
MRC:
The number of alternating current phases.FAAZ
Phase:
Three