MRC:
The element,compound,or mixture of which the case is fabricated,excluding any surface treatment.ADTV
Case Material:
Plastic
MRC:
The number of poles included in the item.AKPX
Pole Quantity:
3
MRC:
Those features,not otherwise specified,which may be required for proper functioning of the item.CBBL
Features Provided:
Adjustable trip release
MRC:
The maximum current load that each pole is rated to carry continuously.CPLM
Maximum Continuous Load Current Rating Per Pole:
800.0 amperes ac all locations and 800.0 amperes dc all locations
MRC:
Indicates the type and value of operating voltage for which each pole is designed to operate,expressed in volts.CPRF
Operating Voltage Type And Rating Per Pole In Volts:
600.0 ac all locations and 250.0 dc all locations
MRC:
Indicates the type and value of the maximum short circuit current that the item will successfully interrupt,per pole,at the specified rated voltage,expressed in amperes.CPRG
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps:
30000.0 ac all locations and 30000.0 dc all locations
MRC:
Indicates the type of electrical condition that will cause the device to trip.CPRH
Circuit Protection Type:
Overcurrent all locations
MRC:
The means by which the trip mechanism is released.CPRJ
Trip Release Method:
Thermal-magnetic all locations
MRC:
Indicates the type and voltage rating required to operate the auxiliary /remotely actuated/ trip actuator,expressed in volts.CPRK
Auxiliary Trip Coil Voltage Type And Rating In Volts:
120.0 ac all locations
MRC:
Denotes the type of trip release action.CPRL
Trip Release Characteristic:
Instantaneous all locations
MRC:
The continuous current rating per pole at which the device must trip in a specified time,expressed in percent.CPRN
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent:
125.0 all locations
MRC:
The means provided to reposition the mechanism so that the device is ready to function.CPRQ
Reset Method:
Manual
MRC:
Indicates the type of mechanism provided for tripping main contacts.CPRR
Main Contact Tripping Mechanism Type:
Trip free
MRC:
Indicates the type and number of actuators provided for manual control.CPRT
Manual Actuator Type And Quantity:
1 toggle
MRC:
Denotes the action imparted by actuator operation.CPRW
Actuator Function:
Trip-reset
MRC:
An indication of the designated position of the actuator.CPRX
Actuator Position Designation:
At pole two
MRC:
The minimum and maximum values of current to which an adjustable trip setting device may be set per pole,expressed in amperes.CPSF
Adjustable Trip Setting Current Range Per Pole In Amps:
+4000.0/+6400.0 ac all locations
MRC:
The working period which the trip release is designed to operate.CQQC
Trip Release Duty Cycle:
Continuous all locations
MRC:
Indicates the type of protection for which the inclosure is designed.CQXF
Inclosure Protection Type For Which Designed:
Dustproof and fungus proof
MRC:
The temperature of the medium surrounding the trip release at which it can be operated continuously.CRCF
Trip Release Ambient Tempurature Rating:
50.0 degrees celsius all locations
MRC:
The cycles per second /hertz/ of the alternating current.FREQ
Frequency In Hertz:
60.0 all locations
MRC:
Indicates the type and number of terminals for providing electrical connection.TTQY
Terminal Type And Quantity:
6 compression