부품 정보
Regualtor valve assembly, 1-1/2" style a failsafe, doulble seat, reverse acting
TXT
묘사:
Temperature Regulating Valve
MRC:
The basic material of which the body is fabricated.AAFZ
Body Material:
Bronze, mil-b-16541
MRC:
The style designation indicating the configuration that most nearly corresponds to the appearance of the body.AAQL
Body Style:
Straight thru
MRC:
The element, compound,or mixture of which the stem is fabricated,excluding any surface treatment.ABEP
Stem Material:
Steel, corrosion resisting, qq-s-763, class 302, 303, 304, 305, 310, or 316
MRC:
Items furnished as accessories which are not specified elsewhere.ABFF
Furnished Items:
Tailpiece w/grooves and union nut
MRC:
A narrative description of the type of end connection.ACKM
First End Connection Type:
Unthreaded internal pipe
MRC:
The style designation indicating the configuration that most nearly corresponds to the appearance of the end.ACKN
First End Style Designator:
Socket w/brazing ring
MRC:
The industrial designation or term used to define the nominal diameter of the pipe the end will accommodate.ACLG
First End Pipe Size Accommodated:
1.500 inches
MRC:
Indicates whether or not the second end is identical to the first end.ACLR
Second End Relationship With First End:
Identical
MRC:
The element,compound,or mixture of which the seating surfaces are fabricated.ACSH
Seat Material:
Steel, corrosion resisting, qq-s-763, class 302, 303, 304, 305, 310, or 316
Face To Face Distance:
7.750 inches
MRC:
The part that controls the flow through the item.ADQU
Flow Control Device:
Disk, dual
MRC:
The element,compound,or mixture of which the flow control device is fabricated.ADQV
Flow Control Device Material:
Steel, corrosion resisting, qq-s-763, class 302, 303, 304, 305, 310, or 316
MRC:
The number of end connections included in the item.ADQZ
End Connection Quantity:
2
MRC:
Indicates the type of renewable seating ring in the item.ADZH
Renewable Seat Ring Type:
Threaded
MRC:
An indication of the action of a two-way valve.AEVM
Two-way Valve Action:
Reverse acting
MRC:
A measurement of the longest dimension of a capillary tube.AEVT
Capillary Tube Length:
300.000 inches
MRC:
The element,compound,or mixture of which the bulb is fabricated.AEVW
Bulb Material:
Copper
MRC:
An indication of whether or not the temperature is adjustable.AEVX
Tempurature Adjustability:
Adjustable
MRC:
The basic design type of the thermostatic element used in transmitting the temperature of a liquid or gas.AEWJ
Thermostatic Element:
Liquid immersion type
MRC:
The national stock number or the identification information of the end equipment for which the item is a part.AGAV
End Application:
Hsu hydraulic starting power
MRC:
A value which expresses the degree of heat or cold as applied to the operation,or limitation of operation,of an item.AZKQ
Tempurature Rating:
Between 130.0 degrees fahrenheit and 160.0 degrees fahrenheit
MRC:
The specification and/or standard of the end connection.BZRS
End Connection Specification/std:
Mil-f-1183 grooved for brazing rings
MRC:
Designates the size of the valve.CCFG
Valve Size:
1.500 inches
MRC:
Those unusual or unique characteristics or qualities of an item not covered in the other requirements and which are determined to be essential for identification.FEAT
Special Features:
Set temperature: 140; flow 45 gpm
MRC:
The document designator of the specification or standard which established the item of supply.ZZZK
Specification Data:
81349 - mil-v-19772 government specification
MRC:
The number,letter,or symbol that indicates the type,style,grade,class,and the like,of an item in a nonidentifying specification or standard.ZZZT
Specification Or Standard:
Ii type and 2 class and 250 series and a design