TXT
묘사:
Circuit Breaker Tripper
MRC:
The number of poles included in the item.AKPX
Pole Quantity:
3
MRC:
Those features,not otherwise specified,which may be required for proper functioning of the item.CBBL
Features Provided:
Adjustable trip release
MRC:
The maximum current load that each pole is rated to carry continuously.CPLM
Maximum Continuous Load Current Rating Per Pole:
400.0 amperes ac all locations
MRC:
Indicates the type and value of operating voltage for which each pole is designed to operate,expressed in volts.CPRF
Operating Voltage Type And Rating Per Pole In Volts:
500.0 ac all locations
MRC:
Indicates the type of electrical condition that will cause the device to trip.CPRH
Circuit Protection Type:
Overcurrent all locations
MRC:
The means by which the trip mechanism is released.CPRJ
Trip Release Method:
Thermal-magnetic all locations
MRC:
Denotes the type of trip release action.CPRL
Trip Release Characteristic:
Instantaneous all locations and time delay all locations
MRC:
The continuous current rating per pole at which the device must trip in a specified time,expressed in percent.CPRN
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent:
150.0 all locations
MRC:
The ultimate time per pole in which the device must trip,expressed in seconds.CPRP
Ultimate Trip Time Per Pole In Seconds:
3600.000 all locations
MRC:
The minimum and maximum values of current to which an adjustable trip setting device may be set per pole,expressed in amperes.CPSF
Adjustable Trip Setting Current Range Per Pole In Amps:
+1900.0/+3500.0 ac all locations
MRC:
The temperature of the medium surrounding the trip release at which it can be operated continuously.CRCF
Trip Release Ambient Tempurature Rating:
50.0 degrees celsius all locations
MRC:
The cycles per second /hertz/ of the alternating current.FREQ
Frequency In Hertz:
60.0 all locations