TXT
묘사:
Refrigeration Condenser
MRC:
The type of service with which the item is designed to be used.ACKL
Media For Which Designed:
Freon 12
MRC:
The element,compound,or mixture of which the shell is fabricated.AEUG
Shell Material:
Steel
MRC:
The element,compound,or mixture of which the head is fabricated,excluding any surface treatment.ARGE
Head Material:
Bronze
MRC:
The number of tubes included on the item.ARNF
Tube Quantity:
196
MRC:
The type of water with which the item is designed to be used.AWCD
Water For Which Designed:
Salt
MRC:
The number of passes provided.AWGE
Pass Quantity:
2
MRC:
The amount of condensing surface area.AWGG
Condensing Surface Area:
655.000 square feet
MRC:
The element,compound,or mixture of which the tube is fabricated,excluding any surface treatment.AWGJ
Tube Material:
Nickel copper alloy
MRC:
A measurement of the longest dimension of a tube between the inside faces of the tube sheets,in distinction from width.AWGK
Tube Effective Length:
6.990 feet
MRC:
An indication of whether of not the tube(s) is provided with fins.AWGL
Tube Fin:
Provided
MRC:
The length of a straight line which passes through the center of the shell,and terminates at the outside circumference.AWKS
Shell Outside Diameter:
16.000 inches
MRC:
Indicates the type of water connection/s/.AWKW
Water Connection Type:
Flange
MRC:
Designates the size of the water connection.AWKZ
Water Connection Size:
5 in. Ips
MRC:
The maximum internal pressure,determined by destruction tests at which the item can be expected to rupture.AWWG
Refrigerant Side Test Minimum Pressure:
350.0 pounds per square inch
MRC:
The maximum internal pressure,determined by destruction tests at which the item can be expected to rupture.AWWH
Water Side Test Minimum Pressure:
300.0 pounds per square inch